The Series MS2 Magnesense® II Differential Pressure Transmitter combines the proven stable piezo technology and the versatility of our original Series MS with additional features to reduce installation time and simplify ordering. Like the original Series MS, the second generation transmitter can be used as a linear pressure output or a linear velocity output with the square root extraction done in the transmitter. Additional parameters have been included to expand the square root capability to include flow measurements.

Supported Baud Rates: 9600, 19200, 38400, 57600, 76800, 115200
Data Size:
Parity: None 
Stop Bits: 1
Service: Air and non-combustible, compatible gases
Wetted Materials: Consult factory 
Typical Accuracy: ±1% FS for 0.15 in w.c. (40 Pa), 0.25 in w.c. (50 Pa), 0.5 in w.c. (125 Pa), 2 in w.c. (500 Pa), 3 in w.c. (750 Pa), 5 in w.c. (1250 Pa), 10 in w.c. (2 kPa), 15 in w.c. (3 kPa), 25 in w.c. (5 kPa), 28 in w.c. (6.975 kPa); ±2% FS for 0.1 in w.c. (25 Pa), 1 in w.c. (250 Pa), and all bi-directional ranges.
Stability: ±1% / year FSO
Temperature Limits: 0 to 150°F (-18 to 66°C)
Pressure Limits: 1 psi max., operation; 10 psi burst
Power Requirements: 10-35 VDC (2-wire), 17-36 VDC or isolated 21.6-33VAC (3-wire)
Output Signals: 4-20 mA (2-wire), 0-5 VDC, 0-10 VDC (3-wire)
Response Time: Adjustable: 0.5 to 15 sec. time constant. Provides a 95% response time of 1.5 to 45 seconds.
Zero and Span Adjustments: Digital push-buttons
Loop Resistance: Current output: 0 to 1250 Ω max; Voltage output: Min. load resistance 1 kΩ
Current Consumption: 40 mA max.
Display (Optional): 5 digit LCD
Electrical Connections: 3-wire removable European style terminal block for 16 to 22 AWG
Electrical Entry: 1/2˝ NPS thread
Process Connection: 3/16˝ ID tubing (5 mm ID); Max. OD 9 mm
Enclosure Rating: IP66
Mounting Orientation: Not position sensitive
Weight: 8.0 oz (230 g)
Agency Approvals: BTL, CE. 

dw-ms2_003.jpg


dw-ms2_004.jpg

• Field selectable ranges and output signal reduce inventory and the chances of ordering an incorrect part 

• BACnet or Modbus® serial communications reduce wiring cost by daisy-chaining the transmitters 

• Our integral field-upgradeable display or plug-in remote display tool save upfront material cost and allow for local viewing of measurements

• Filter monitoring in air handler units 

• Building pressure in pharmaceutical-semi-conductor clean rooms 

• Duct static pressure in commercial buildings 

• Air velocity/flow in VAV systems